The Effect of Wind on the Performance of the Three Short Natural Draft Dry Cooling Towers in an In-line Arrangement

aut.relation.conferenceAPSRC, 2018en_NZ
aut.researcherAnderson, Timothy
dc.contributor.authorKhamooshi, Men_NZ
dc.contributor.authorAnderson, Ten_NZ
dc.contributor.authorNates, Ren_NZ
dc.date.accessioned2019-04-15T02:35:30Z
dc.date.available2019-04-15T02:35:30Z
dc.date.copyright2018en_NZ
dc.date.issued2018en_NZ
dc.description.abstractNatural draft dry cooling tower (NDDCT) are a favourable choice for the cooling system of concentrated solar thermal power (CSP) plants located in arid regions with high solar radiation. However, additional cooling towers may be required as the capacity of the CSP plants is increased. The geometrical arrangement of the NDDCTs is an influencing parameter on the thermo-flow performance of the entire system. The aim of this study was to investigate the effect of tower spacing and crosswind velocity on the performance of three short NDDCTs in an in-line layout. The results showed that there is a noticeable interaction between the towers at different tower spacings and crosswind conditions. In the no-wind condition, the cooling performance of both towers is reduced with a small tower-spacing, as this limits the air supply and the airflow across the heat exchangers in both towers. However, in windy conditions, the redirection of flow due to the layout of the cooling towers can improve the performance of the towers. The performance of the middle and leeward tower is improved compared to the windward tower. This improvement becomes weaker with increasing tower spacing.en_NZ
dc.identifier.citationAPSRC, 2018, ‘Proceedings of the Asia Pacific Solar Research Conference 2018, Retrieved from: http://apvi.org.au/solar-research-conference/wp-content/uploads/2019/03/Anderson-Mehrdad-The-Effect-of-Wind-on-the-Performance-Natural-Draft-Dry-Cooling-Towers-in-an-Inline-Arrangement.pdf
dc.identifier.urihttps://hdl.handle.net/10292/12447
dc.publisherAustralian PV Institute (APVI)
dc.relation.urihttp://apvi.org.au/solar-research-conference/wp-content/uploads/2019/03/Anderson-Mehrdad-The-Effect-of-Wind-on-the-Performance-Natural-Draft-Dry-Cooling-Towers-in-an-Inline-Arrangement.pdf
dc.rightsAuthors retain the right to place his/her publication version of the work on a personal website or institutional repository for non commercial purposes. The definitive version was published in (see Citation). The original publication is available at (see Publisher’s Version).
dc.rights.accessrightsOpenAccessen_NZ
dc.titleThe Effect of Wind on the Performance of the Three Short Natural Draft Dry Cooling Towers in an In-line Arrangementen_NZ
dc.typeConference Contribution
pubs.elements-id358364
pubs.organisational-data/AUT
pubs.organisational-data/AUT/Design & Creative Technologies
pubs.organisational-data/AUT/Design & Creative Technologies/Engineering, Computer & Mathematical Sciences
pubs.organisational-data/AUT/PBRF
pubs.organisational-data/AUT/PBRF/PBRF Design and Creative Technologies
pubs.organisational-data/AUT/PBRF/PBRF Design and Creative Technologies/PBRF ECMS
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Effect of Wind on the Performance - Revised.pdf
Size:
1.09 MB
Format:
Adobe Portable Document Format
Description:
Conference contribution
License bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
AUT Grant of Licence for Tuwhera Aug 2018.pdf
Size:
276.29 KB
Format:
Adobe Portable Document Format
Description: